Features
◎ Din-rail mounting,4 Modules 72mm Width
◎ Pulse Output
◎ LCD with backlight
◎ Double-tariff
◎ Multi-measurement:kWh,W,V,A,Hz,etc
◎ With supper capacitor,the LCD is also legible twice within a period of 2 weeks without power supply.
◎ When the phase conductor is missing or the current direction is wrong ‘false’ and the corresponding phase conductor are indicated on the display.
Technical Specifications
Essential information
| Model | Type | Rated Voltage(Un) | Rated Current(Ib) | Pulse constant | Frequency | Dimensions (H×W×D)mm |
| SXY12D-3×80A | Three Phase | 3×230V/440V | 10A(80)A | 1000imp/kWh | 50Hz | 82.5×72×62.5 |
Electrical Characteristics
| Operational Voltage | Extended Range | Internal Consumption | Accuracy Class |
| 0.9Un~1.1Un | 0.8Un~1.15Un | <0.5W | Class B |
Performance Criteria
| Storage and operating humidity | Annual average value≤75% |
| Operating temperature | -25℃~+55℃ |
| Limiting operating temperature | -40℃~+70℃ |
| Storage and transport temperature | -40℃~+70℃ |
| International standard | IEC62053-21/EN0470-1/EN50470-3 |
| Mechanical environment | M1 |
| Electromagnetic environment | E2 |
| Protection class | IP51(indoor) |
Typical connection
| Maximum conductor cross section | |
| L | 25mm² |
| N | 16mm² |
| SO | 6mm² |